蘇州禾久實(shí)電氣設(shè)備有限公司
頂
置
式
空
調(diào)
說(shuō)
明
書
HSDZA-600W 工業(yè)機(jī)柜空調(diào)使用說(shuō)明書
目 錄
1. 安全注意事項(xiàng)·······················································································1
2. 安裝要求 ·····························································································1
2-1 安裝位置·························································································2
2-2 安裝方法·························································································3
2-3 電器配線························································································6
2-4 機(jī)器排水·························································································6
3. 啟動(dòng)與運(yùn)轉(zhuǎn)···························································································6
3-1 運(yùn)行前后注意事項(xiàng)···········································································6
3-2 機(jī)器操作說(shuō)明··················································································7
4. 維護(hù)與保養(yǎng)·························································································7
4-1 定期清潔·······················································································7
4-2 長(zhǎng)時(shí)間停用時(shí)注意··········································································7
5. 故障排除·····························································································8
附錄
一······································································································9
附錄
二······································································································9
1. 安 全 注 意 事 項(xiàng)
⑴ 當(dāng)用戶對(duì)本空調(diào)器進(jìn)行各種操作時(shí),請(qǐng)先詳讀本使用手冊(cè),并注意本手冊(cè)
中所提到的注意事項(xiàng),以避免出現(xiàn)意外情況;
⑵ 請(qǐng)勿用濕手操作,以免引起觸電;
⑶ 當(dāng)需要保養(yǎng)或維護(hù)時(shí),請(qǐng)先切斷所有電源以免引起觸電事故;
⑷ 空調(diào)器上不易放置任何物品,以免滑落造成人員傷害;
⑸ 當(dāng)機(jī)器在運(yùn)轉(zhuǎn)時(shí),請(qǐng)勿將手指或任何物品伸入進(jìn)、出風(fēng)口,以避免人員受
傷或機(jī)器損壞;
⑹ 本機(jī)器露天放置做好密封處理以免雨水進(jìn)入機(jī)體內(nèi),并且也不適宜于安裝
在振動(dòng)較大或者移動(dòng)的設(shè)備上,當(dāng)客戶必需安裝在此種條件下時(shí),請(qǐng)務(wù)必致
電本公司咨詢;
⑺ 本空調(diào)器為工業(yè)用設(shè)備,當(dāng)須用于動(dòng)植物或食品等方面之特殊用途時(shí),請(qǐng)
致電本公司咨詢;
⑻ 禁止自行改裝、修理、拆卸或者移裝,欲進(jìn)行上述動(dòng)作前請(qǐng)先向?qū)I(yè)人員
咨詢,以防意外發(fā)生。
2. 安裝要求
本空調(diào)器為頂置式系列(圖一),為使機(jī)組能在理想的狀況下工作,在安裝
上請(qǐng)注意以下要求:
圖一 頂置式
電控箱
冷氣機(jī)
2-1 安裝位置
⑴ 空調(diào)器需安裝在周圍空氣品質(zhì)良好的環(huán)境中,請(qǐng)勿放置于有腐蝕性氣體、
可燃性氣體、粉塵類氣體、油污類氣體等品質(zhì)較差的空氣中;
⑵ 空調(diào)器應(yīng)安裝在通風(fēng)良好且熱量易于排放的地方,因?yàn)榭照{(diào)器運(yùn)行時(shí)會(huì)
排出熱量,如果空調(diào)器周圍排氣不暢很容易導(dǎo)致其周圍的溫度升高,這將影
響空調(diào)器的制冷效果。見圖二,空調(diào)器進(jìn)、排風(fēng)口離墻面的間距應(yīng)大于
500mm;
⑶ 空調(diào)器周圍請(qǐng)勿放置雜物,以保持空氣暢通流通;
⑷ 本空調(diào)器不宜放置于陽(yáng)光可以直射的地方,避免因陽(yáng)光照射而吸熱,影
響冷卻效果。
⑸ 請(qǐng)安裝本空調(diào)器于周圍溫度在 45℃以下的范圍之內(nèi)高溫系列 55℃以下;
⑹ 本機(jī)安裝時(shí)請(qǐng)注意上下位置擺放正確,絕對(duì)不能倒置安裝,前后左右必
須保持垂直,其傾斜角不大于 5°如圖三所示;
⑺ 控制箱內(nèi)正對(duì)出風(fēng)口的電器元件與出風(fēng)口的最小距離應(yīng)大于 200mm,因
距離太近電器元件表面易產(chǎn)生水膜現(xiàn)象,從而導(dǎo)致電器故障的發(fā)生。若無(wú)法
避免,請(qǐng)?jiān)陔娖髟霸黾右粔K隔熱材料;并且箱內(nèi)出風(fēng)口四周的電器元件
與出風(fēng)口應(yīng)保持一定的距離,以便減小箱內(nèi)空氣的流通阻力。
⑻ 當(dāng)空調(diào)器工作時(shí),電控箱四周應(yīng)該密封,箱門盡量較少打開次數(shù),以便
箱體內(nèi)空氣的溫、濕度能控制在較為理想的狀態(tài)下。
圖二
圖 三
錯(cuò) 誤 正 確 錯(cuò) 誤 正 確
2-2 安裝方法
⑴ 當(dāng)機(jī)組在搬運(yùn)、裝卸時(shí),請(qǐng)始終保持設(shè)備處于垂直直立狀態(tài),不要將設(shè)
備長(zhǎng)期放在露天場(chǎng)所;
⑵ 為使空調(diào)器的冷卻效果最佳,請(qǐng)將機(jī)組直接安裝在電氣柜的外壁上或頂
上(根據(jù)用戶所選機(jī)型來(lái)決定),請(qǐng)勿采用風(fēng)管的形式進(jìn)行送風(fēng),如若確實(shí)
需要采用風(fēng)管送風(fēng),請(qǐng)先咨詢本公司技術(shù)工程師;
⑶ 空調(diào)器在安裝之前,請(qǐng)先確認(rèn)好安裝位置的強(qiáng)度是否能承載機(jī)組,以免
造成人員受傷及設(shè)備損壞,當(dāng)安裝在電氣柜門上時(shí),最好該扇箱門能固定不
動(dòng),當(dāng)需要打開時(shí)請(qǐng)先確認(rèn)好加在門上的重量不會(huì)使整個(gè)電氣柜傾倒;
⑷ 電氣柜上必須開孔,以便使冷風(fēng)能進(jìn)入電控箱內(nèi),具體的開口尺寸請(qǐng)參
見圖五;
⑸ 箱體開孔時(shí)請(qǐng)嚴(yán)格參照開口尺寸進(jìn)行,孔口處的毛刺必須清除,以免劃
傷機(jī)組;
⑹ 當(dāng)長(zhǎng)期使用時(shí)請(qǐng)注意安裝螺栓是否損壞或脫落,若有而未加處理,將有
可能導(dǎo)致機(jī)器掉落而損壞;
⑺ 具體的安裝尺寸方式如下:
安裝方式一:
起吊環(huán)
電控箱
XPE 保溫棉
開口
a. 準(zhǔn)備好該類安裝方式的空
調(diào)器
b. 按照開口尺寸在電控箱頂部開好
口,并粘貼好 XPE 保溫綿(若機(jī)器
底部自帶,則不需),然后擰下機(jī)組
底部四角上的螺帽,并確定好螺栓的
伸出長(zhǎng)度(約 15mm)。
電控箱
排水口
C 通過(guò)起吊環(huán)用起吊機(jī)吊起機(jī)組(若
無(wú)起吊環(huán)則需人工搬裝),把電源線從
電線孔伸入電控箱內(nèi),然后對(duì)好螺栓孔
輕輕放下機(jī)器,隨后在電控箱內(nèi)的螺栓
上墊上墊圈并擰緊螺帽。
電控箱內(nèi)側(cè)
d 在機(jī)組側(cè)面排水口處連接好排水
管,用抱箍固定好,另一端請(qǐng)引入排水
溝或蓄水桶內(nèi),檢測(cè)電源是否與機(jī)組匹
配,然后接上電源即可開機(jī)使用。
排水管
2-3 電器配線:
⑴ 機(jī)組安裝好后請(qǐng)先檢查電源電壓值是否保持在容許額定值內(nèi),請(qǐng)避免電壓值過(guò)高或
過(guò)低,若所提供的電壓在額定值±10%以內(nèi),本機(jī)組可正常使用;
⑵ 空調(diào)的電器箱在機(jī)體內(nèi)部,非專業(yè)維修人員請(qǐng)勿打開電器箱進(jìn)行操作。機(jī)組引出一
根電源線,當(dāng)安裝好后無(wú)需另外接線,將插頭插入電控箱內(nèi)的電源插座即可;
⑶ 在機(jī)組的電器回路上請(qǐng)自行安裝斷路器或保護(hù)裝置;
⑷ 請(qǐng)準(zhǔn)備本機(jī)專用電源插座,不要在同一個(gè)插座上使用過(guò)多電器裝置,否則容易使電
源超出負(fù)載,引發(fā)事故。
2-4 機(jī)器排水:
本機(jī)器自身有除濕功能,當(dāng)機(jī)器運(yùn)行時(shí),它會(huì)慢慢除去電控箱內(nèi)空氣中的部分水分,這
部分水氣就會(huì)以液態(tài)的形式排出,排水管就起到排出這部分水的作用,排水管的連接請(qǐng)
注意以下幾點(diǎn):(帶自蒸發(fā)系統(tǒng)的機(jī)組配備防溢水管)
⑴ 請(qǐng)先在機(jī)器排水口上連接好短接頭,然后把配給的軟管連接上,再用抱箍緊固好連
接處;
⑵ 根據(jù)實(shí)際情況排水軟管長(zhǎng)度適當(dāng)即可,過(guò)長(zhǎng)部分請(qǐng)切除;
⑶ 排水軟管請(qǐng)勿折彎、壓扁、阻塞或出口高于進(jìn)口,以免排水不暢,從而導(dǎo)致機(jī)器內(nèi)
產(chǎn)生淤水嚴(yán)重時(shí)產(chǎn)生外溢,引起空調(diào)器或者電氣柜故障。
3. 啟動(dòng)與運(yùn)行
3-1 運(yùn)行前后注意事項(xiàng)
⑴ 啟動(dòng)前請(qǐng)先檢查排水管是否已經(jīng)連接到位,電控箱門是否關(guān)嚴(yán),若均已到位即可插
上電源開始工作;
⑵ 當(dāng)在運(yùn)轉(zhuǎn)中需重新啟動(dòng)空調(diào)器時(shí),請(qǐng)間隔 3 分鐘以上,倘若頻繁啟動(dòng)且間隔時(shí)間過(guò)
短會(huì)引起機(jī)器損傷;
⑶ 當(dāng)空調(diào)器傾斜時(shí)請(qǐng)勿開啟,避免漏水、觸電等情況發(fā)生;
⑷ 空調(diào)器在出廠時(shí)溫度點(diǎn)已經(jīng)設(shè)定好為 30℃,若需重新設(shè)定時(shí)請(qǐng)控制在允許范圍之內(nèi)
設(shè)定,以免引起機(jī)器運(yùn)行不正常;
⑸ 當(dāng)機(jī)器有異常噪音或異味(焦臭)等現(xiàn)象出現(xiàn)時(shí),請(qǐng)馬上關(guān)閉空調(diào)器,并請(qǐng)專業(yè)人
員進(jìn)行檢查維修。
簡(jiǎn)介:
BTW-289+系列溫控器采用小型化、IP65 等級(jí)面板防護(hù)設(shè)計(jì),體積小重量輕,操作簡(jiǎn)捷安裝方便。適用于小型機(jī)柜空
調(diào)系統(tǒng)的溫度控制。
主要功能
1. 制冷,風(fēng)機(jī)自動(dòng)控制
2. 壓縮機(jī)智能保護(hù)
3. 多種故障告警,超高溫,低溫告警,系統(tǒng)高壓報(bào)警,缺氟報(bào)警
4. 外部開關(guān)量輸入檢測(cè),繼電器輸出告警,常開,常閉點(diǎn)自由配置
5. 標(biāo)準(zhǔn) RS485 通訊接口,Modbus RTU 通訊協(xié)議
規(guī)格尺寸
1.前面板尺寸: 長(zhǎng) 78 x 寬 34.5(毫米) 2.安裝開孔尺寸:長(zhǎng) 71 x 寬 29(毫米)
3.整機(jī)尺寸: 長(zhǎng) 78 x 寬 34.5 x 深 71(毫米) 4.傳感器線長(zhǎng):1 米(含探頭長(zhǎng)度)
主要技術(shù)指標(biāo)
感溫元件:NTC 3435/10K 電源電壓:交流型:AC220V±20% 50HZ
設(shè)定范圍:0 ~50℃ 接線端子:連接 2*1.5mm 2顯示范圍:-40~99℃ 或 1*2.5mm 2
的導(dǎo)線
工作環(huán)境:-10~45℃ 負(fù)載電流:壓縮機(jī) 16A,風(fēng)機(jī) 10A,告警 5A
存儲(chǔ)溫度:-30~70℃ 外 殼:PC + ABS 阻燃
濕 度:5~85%RH (不結(jié)露) 防護(hù)等級(jí):IP65(前面板)
操作指南
顯示說(shuō)明
顯示屏信號(hào)說(shuō)明
圖標(biāo) 功能 亮 滅 閃爍
壓縮機(jī) 啟動(dòng) 停止 準(zhǔn)備制冷,壓縮機(jī)正在延時(shí)保護(hù)
電加熱 運(yùn)行 ---- 加熱延時(shí)開啟
風(fēng)機(jī) 運(yùn)行 停止 風(fēng)機(jī)延時(shí)開啟
set 設(shè)置 參數(shù)設(shè)置狀態(tài) 測(cè)控狀態(tài) ----
+ 強(qiáng)啟動(dòng) 強(qiáng)制啟動(dòng)壓縮機(jī) 退出強(qiáng)啟動(dòng) ----面板數(shù)碼管說(shuō)明
3 位彩色數(shù)碼管顯示測(cè)量溫度值和告警代碼;
告警代碼
序 號(hào) 顯示代碼 說(shuō) 明
1 “E01” 溫控傳感器故障(短路或斷路)
3 “E02” 蒸發(fā)器傳感器故障(短路或斷路)
3 “E03” 系統(tǒng)缺氟保護(hù)
4 “Hi” 高溫告警
5 “Lo” 低溫告警
8 “LA” 外部無(wú)源數(shù)字量輸入告警(系統(tǒng)高壓告警)
10 “FrE 蒸發(fā)器凍結(jié)保護(hù)
按鍵操作
系統(tǒng)參數(shù)設(shè)置
·系統(tǒng)參數(shù)設(shè)置界面進(jìn)入:
設(shè)置溫度:
測(cè)控狀態(tài)下,長(zhǎng)按[set]3s,出現(xiàn)[St],再按[set],出現(xiàn)制冷溫度,按〖▲〗或〖▼〗鍵可對(duì)參數(shù)進(jìn)行設(shè)置,設(shè)置
完成后再按[RST]鍵,或者 30s 無(wú)按鍵操作,自動(dòng)保存并回到正常測(cè)控狀態(tài)。
設(shè)置內(nèi)部參數(shù):
測(cè)控狀態(tài)下,長(zhǎng)按[set]3s,出現(xiàn)[St], 按〖▲〗出現(xiàn) Po,再按[set],顯示 0,按〖▲〗或〖▼〗鍵將 Po 設(shè)置
到 55,再按[set],返回 Po,此時(shí)按上下鍵,即可選擇其他參數(shù)進(jìn)行配置。
工作參數(shù)代碼及設(shè)置說(shuō)明如下表所示:
參數(shù)代碼 設(shè)置功能 設(shè)定范圍 說(shuō)明 出廠設(shè)定值
St 制冷溫度設(shè)定 15~50℃ 30
Po 密碼 0~99 55 固定不可調(diào) 0
管理員參數(shù)(需要正確的密碼,Po=55)
F00 溫差 1~ 20℃ 5
F01 高溫報(bào)警溫度-5~60℃
高溫/低溫
設(shè)定間隔 1℃
50
F02 低溫報(bào)警溫度 5
F03 蒸發(fā)風(fēng)機(jī)溫度設(shè)定 0~40℃ 26
F04 蒸發(fā)風(fēng)機(jī)溫差 1~ 9℃ 2
F05 溫控探頭校正 -9~9℃ 0
F06 蒸發(fā)器探頭校正 -9~9℃ 0
F07 高溫報(bào)警失效 0~1 0:禁用;1:啟用 1
F08 低溫報(bào)警失效 0~1 0:禁用;1:啟用 1
F09 系統(tǒng)缺氟失效 0~1 0:禁用;1:啟用 1
F10 蒸發(fā)器探頭使能設(shè)定 0~1 0:禁用;1:啟用 0
F11 壓縮機(jī)工作模式 0~1
0:自動(dòng)模式(啟用壓縮機(jī))
1:禁用模式
0
F12 風(fēng)機(jī)工作模式 0~1
0:溫控模式
1:常開模式
1
F13 外部輸入告警模式 0~1
0:常閉;
1:常開
0
F14 蜂鳴器報(bào)警 0~1 0:禁用;1:啟用 1
F15 壓縮機(jī)開機(jī)延時(shí)時(shí)間 1~5 分鐘 3
F16 壓縮機(jī)最短持續(xù)運(yùn)行時(shí)間 1~5 分鐘 3
F17 系統(tǒng)開關(guān)機(jī) 0:通電關(guān)機(jī),1:通電開機(jī) 1
F18 RS485 波特率設(shè)定 0~3
0:4800bps
1:9600bps
2:19200bps
3:115200bps
3
F19 設(shè)備地址 1~64 1
查看蒸發(fā)器溫度
在顯示當(dāng)前溫度時(shí)按一下〖▲〗鍵, 數(shù)碼管顯示制冷設(shè)置溫度值,1S 后恢復(fù)顯示當(dāng)前溫度值。
在顯示當(dāng)前溫度時(shí)按一下〖▼〗鍵, 數(shù)碼管顯示蒸發(fā)器探頭溫度值,1S 后恢復(fù)顯示當(dāng)前溫度值。
控制功能說(shuō)明:
壓縮機(jī)控制
◇當(dāng)測(cè)量溫度 ≥【制冷設(shè)定溫度】 + 【溫差】,且壓縮機(jī)停機(jī)時(shí)間大于【壓縮機(jī)開機(jī)延時(shí)時(shí)間】,壓縮機(jī)開啟;
◇當(dāng)測(cè)量溫度 ≤【設(shè)定溫度】,且壓縮機(jī)開機(jī)時(shí)間大于【壓縮機(jī)最短持續(xù)運(yùn)行時(shí)間】,壓縮機(jī)關(guān)閉;
例如:【制冷設(shè)定溫度】為 25 度, 【溫差】為 2 度,則當(dāng)溫控傳感器檢測(cè)溫度高于 27 度時(shí)啟動(dòng)壓縮機(jī),溫度
低于 25 度時(shí)關(guān)閉壓縮機(jī),將溫度控制在 25~27 度之間;
◇壓縮機(jī)強(qiáng)制啟動(dòng):
1.在壓縮機(jī)關(guān)閉情況下,按住〖RST〗鍵 5 秒不放,可以強(qiáng)制啟動(dòng)壓縮機(jī)。在壓縮機(jī)強(qiáng)制啟動(dòng)狀態(tài)下,按住〖RST〗
鍵 5
秒不放,可以取消強(qiáng)制啟動(dòng)壓縮機(jī),壓縮機(jī)恢復(fù)正常運(yùn)行。
2.壓縮機(jī)在強(qiáng)制啟動(dòng)狀態(tài)下持續(xù)運(yùn)行 30min 后,壓縮機(jī)恢復(fù)正常運(yùn)行。
壓縮機(jī)延時(shí)保護(hù)
◇運(yùn)行過(guò)程中壓縮機(jī)停機(jī),必須經(jīng)過(guò)【壓縮機(jī)開機(jī)延時(shí)時(shí)間】才能再次啟動(dòng);
◇運(yùn)行過(guò)程中壓縮機(jī)開啟,必須經(jīng)過(guò)【壓縮機(jī)最短持續(xù)運(yùn)行時(shí)間】才能以實(shí)際情況停機(jī);
風(fēng)機(jī)控制:
控制器在運(yùn)行過(guò)程中,風(fēng)機(jī)按照如下規(guī)則運(yùn)行:
? 如果風(fēng)機(jī)設(shè)定為常開,則送風(fēng)機(jī)始終開啟;
? 如果風(fēng)機(jī)設(shè)定為溫控則風(fēng)機(jī)根據(jù)溫控傳感器溫度進(jìn)行控制。控制條件如下:
◇當(dāng)測(cè)量溫度 ≥【蒸發(fā)風(fēng)機(jī)設(shè)定溫度】 + 【蒸發(fā)風(fēng)機(jī)溫差】,且風(fēng)機(jī)已經(jīng)停機(jī)時(shí)間大于 1 分鐘,風(fēng)機(jī)開啟;
◇當(dāng)測(cè)量溫度 ≤【蒸發(fā)風(fēng)機(jī)設(shè)定溫度】,且風(fēng)機(jī)開機(jī)時(shí)間大于 1 分鐘,風(fēng)機(jī)關(guān)閉;
例如:【蒸發(fā)風(fēng)機(jī)設(shè)定溫度】為 23 度, 【蒸發(fā)風(fēng)機(jī)溫差】為 2 度,則當(dāng)溫控傳感器檢測(cè)溫度高于 25 度時(shí)啟動(dòng)風(fēng)機(jī),
溫度低于 23 度時(shí)關(guān)閉風(fēng)機(jī),將溫度控制在 23~25 度之間;
蜂鳴器功能
每按鍵一次蜂鳴器鳴叫一聲,在參數(shù)設(shè)置確認(rèn)時(shí)長(zhǎng)鳴一次,在進(jìn)行無(wú)效操作時(shí)蜂鳴器鳴叫三聲;當(dāng)系統(tǒng)出現(xiàn)故
障
或有外部報(bào)警輸入時(shí),如果參數(shù) F13=0,關(guān)閉蜂鳴器報(bào)警功能,蜂鳴器不鳴叫報(bào)警;如果參數(shù) F13=1,則蜂鳴器
連續(xù)鳴叫報(bào)警; 系統(tǒng)恢復(fù)正常后,自動(dòng)消除蜂鳴器報(bào)警狀態(tài).高溫、低溫超溫告警
1.當(dāng)測(cè)量溫度 ≥ 【高溫報(bào)警溫度】,將產(chǎn)生高溫報(bào)警, 當(dāng)測(cè)量溫度 ≤ 【高溫報(bào)警溫度】,控制
器取消高溫告警;
2.當(dāng)測(cè)量溫度 ≤ 【低溫報(bào)警溫度】,將產(chǎn)生低溫報(bào)警, 當(dāng)測(cè)量溫度 ≥ 【低溫報(bào)警溫度】+ 2 度,控制
器取消低溫告警;
外部輸入告警 (系統(tǒng)高壓告警)
外部數(shù)字量有以下幾種輸入方式:;
常開:表示在正常情況下外部告警輸入信號(hào)為開路狀態(tài),閉合則產(chǎn)生告警。
常閉:表示在正常情況下外部告警輸入信號(hào)為閉合狀態(tài),開路則產(chǎn)生告警。
系統(tǒng)高壓告警: 如果 1 小時(shí)內(nèi)連續(xù)出現(xiàn) 3 次壓力告警,將一直關(guān)閉壓縮機(jī)。手動(dòng)重新上電可以解除告警。
溫度值校正功能
當(dāng)測(cè)量溫度值與傳感器安裝位置實(shí)際溫度有誤差,可通過(guò)【溫度修正參數(shù)】進(jìn)行校正,校正范圍±9.9℃;按一
次〖▲〗
或〖▼〗鍵調(diào)整溫度校正值增或減 01℃,按住不放則快速調(diào)整;
系統(tǒng)缺氟(漏氟)保護(hù):
當(dāng)壓縮機(jī)啟動(dòng) 5 分鐘后,檢測(cè)溫控傳感器、蒸發(fā)器傳感器溫度,,如果溫控傳感器溫度高于蒸發(fā)器傳感器溫度 5
度以
上溫差,判定系統(tǒng)正常,否則認(rèn)定為缺氟保護(hù)(漏氟),并顯示報(bào)警代碼“E03”。強(qiáng)制關(guān)閉壓縮機(jī)。
如果 1 小時(shí)內(nèi)連續(xù)出現(xiàn) 3 次缺氟保護(hù),將一直關(guān)閉壓縮機(jī)。手動(dòng)重新上電可以解除告警。
蒸發(fā)器凍結(jié)保護(hù):
當(dāng)壓縮機(jī)啟動(dòng) 1 分鐘后,檢測(cè)蒸發(fā)器傳感器溫度,如果蒸發(fā)器傳感器溫度小于等于1 度并保持 5 秒,判定蒸發(fā)器
凍結(jié)保護(hù),并顯示報(bào)警代碼“FrE”。控制器強(qiáng)制關(guān)閉壓縮機(jī)并開啟送風(fēng)機(jī)。當(dāng)蒸發(fā)器的溫度上升 8 度以上,退出凍
結(jié)保護(hù),控制器恢復(fù)正常工作。
告警輸出
告警列表說(shuō)明
故 障
檢測(cè)
條件
推遲
持續(xù)
時(shí)間
復(fù)位
操作
動(dòng)作
溫控傳感器故障 隨時(shí) 0s 2s 自動(dòng)
開壓縮機(jī)、停電加熱,溫控模式下開蒸發(fā)風(fēng)機(jī);
取消缺氟保護(hù)告警
蒸發(fā)溫度傳感器故障 隨時(shí) 0s 2s 自動(dòng) 取消缺氟保護(hù)告警
壓力保護(hù) 隨時(shí) 0s 5s 手動(dòng) 停壓縮機(jī)
缺氟保護(hù) 壓縮機(jī)啟動(dòng) 5min 5s 手動(dòng) 停壓縮機(jī)
高溫告警 隨時(shí) 0s 5s 自動(dòng) 只告警
低溫告警 隨時(shí) 0s 5s 自動(dòng) 只告警
蒸發(fā)凍結(jié)保護(hù) 壓縮機(jī)啟動(dòng) 1min 5s 自動(dòng) 停壓縮機(jī),開始送風(fēng)機(jī)
告警接口說(shuō)明
信號(hào)名稱 說(shuō)明
NO 故障輸出(故障時(shí)斷開,正常時(shí)閉合)
NC 故障輸出(故障時(shí)閉合,正常時(shí)斷開)
C 公共端
控制器接線示意圖
安 裝步驟
第1步: 將控制器嵌入孔中;
第2步: 通過(guò)在設(shè)備的導(dǎo)軌方向
滑動(dòng)支架來(lái)固定控制器,直到將控制器壓實(shí)在面板上;
電氣連接
敬告:
◆電氣接線操作必須由有資質(zhì)的技術(shù)人員來(lái)完成。
◆使用規(guī)定電源類型以外的電源可能會(huì)給系統(tǒng)帶來(lái)嚴(yán)重?fù)p害;
◆盡可能將傳感器、開關(guān)量輸入信號(hào)線與感性負(fù)載線、電源線分開排線,以避免電磁干擾。絕不能將電源線(包括電力線)
和
485 通訊協(xié)議
本產(chǎn)品支持標(biāo)準(zhǔn) Modbus RTU 協(xié)議,支持標(biāo)準(zhǔn) RS485 接口,可與所有支持標(biāo)準(zhǔn) RS485 接口的設(shè)備通訊。
1 通訊參數(shù):默認(rèn)9600,N,8,1,波特率可選;
2. 支持保持寄存器讀寫,支持03,06,16功能碼;
3. 建議應(yīng)答超時(shí)時(shí)間設(shè)置大于1000ms;
4 建議輪詢時(shí)間間隔設(shè)置大于100ms;
5. R:只讀,W:只寫,R/W:可讀可寫。
6. 下表格是具體寄存器參數(shù)及說(shuō)明:
地址 功能說(shuō)明 預(yù)設(shè) 範(fàn)圍 單位 讀寫
0 柜溫探頭溫度(實(shí)際溫度×10) - -400~990 ℃ R
1 蒸發(fā)器探頭溫度(實(shí)際溫度×10) - -400~990 ℃ R
2 制冷繼電器狀態(tài) - 0:斷開 1:閉合 - R
3 風(fēng)機(jī)繼電器狀態(tài) - 0:斷開 1:閉合 - R
4 報(bào)警繼電器狀態(tài) - 0:斷開 1:閉合 - R/W
5 制冷溫度設(shè)定值 30 15~50 ℃ R/W
6 控制回差設(shè)定值 5 1~20 ℃ R/W
7 高溫報(bào)警溫度 50 1~60 ℃ R/W
8 低溫報(bào)警溫度 5 1~60 ℃ R/W
9 蒸發(fā)風(fēng)機(jī)溫度設(shè)定 26 0~40 ℃ R/W
10 蒸發(fā)風(fēng)機(jī)溫差 2 1~5 ℃ R/W
11 蒸發(fā)器探頭使能設(shè)定 0 0:禁用 1:?jiǎn)⒂?- R/W
12 壓縮機(jī)工作模式 0 0:自動(dòng) 1:禁用 - R/W
13 風(fēng)機(jī)工作模式 1 0:受控 1:常開 - R/W
14 外部輸入告警模式 0 0:常閉 1:常開 - R/W
15 蜂鳴器報(bào)警 1 0:禁用 1:?jiǎn)⒂?- R/W
16 壓縮機(jī)開機(jī)延時(shí)時(shí)間 3 1~5 Min R/W
17 壓縮機(jī)最短持續(xù)運(yùn)行時(shí)間 3 1~5 Min R/W
18 系統(tǒng)上電開關(guān)機(jī) 1
0:通電關(guān)機(jī)
1:通電開機(jī)
- R/W
19 RS485 波特率設(shè)定 1
0:4800
1:9600
2:19200
3:115200
- R/W
20 從機(jī)地址(注意:更改之后,上位機(jī)讀取
軟件要相應(yīng)的更改從機(jī)地址)
1 1~64 - R/W
21 遠(yuǎn)程開關(guān)機(jī)(注意:遠(yuǎn)程關(guān)機(jī)狀態(tài)下,長(zhǎng)
按[SET]鍵開機(jī))
1
0:關(guān)機(jī)
1:開機(jī)
- R/W
4.維護(hù)與保養(yǎng)
請(qǐng)定期檢查排水管,并確定無(wú)堵塞現(xiàn)象,若排水不良易造成空調(diào)器漏水。請(qǐng)定期清洗空
氣過(guò)濾網(wǎng)和冷凝器。對(duì)于機(jī)器上安裝的是尼龍濾網(wǎng)的可直接從側(cè)面拔出
4-1 定期清潔
⑴ 本公司濾網(wǎng)有兩種樣式,一種為尼龍濾網(wǎng),可直接從側(cè)面拆下,用洗滌水清洗干凈,
并晾干后按原樣裝回,一般每周需清洗一次;另一種為濾芯式濾網(wǎng)(見圖九),當(dāng)環(huán)境
油污或粉塵大濾芯清洗不干凈時(shí),需要更換新的濾芯,一般半月需要更換一次,;
⑵ 請(qǐng)用中性清洗劑擦拭機(jī)體,避免使用硬刷及酸性清洗劑清洗,嚴(yán)禁用水沖洗空調(diào)器,
以防發(fā)生觸電事故;
4-2 長(zhǎng)時(shí)間停用時(shí)注意
⑴ 請(qǐng)切斷電源,以防意外;
⑵ 清理冷凝器、過(guò)濾網(wǎng)及內(nèi)部油污;
⑶ 請(qǐng)對(duì)機(jī)器采取防塵措施,延長(zhǎng)機(jī)器使用壽命。
5. 故障排除
故障狀況 1 電源接通后,室內(nèi)、室外風(fēng)機(jī)不運(yùn)轉(zhuǎn),溫控器不顯示
可能原因
※保險(xiǎn)絲熔斷
※停電或無(wú)電源
狀況排除
※更換保險(xiǎn)絲
※檢查電源狀況
故障狀況 2 過(guò)載指示燈亮
可能原因
※環(huán)境溫度過(guò)高,導(dǎo)致壓縮機(jī)熱保護(hù)
※過(guò)濾網(wǎng)堵塞或者冷凝器過(guò)臟,導(dǎo)致壓縮機(jī)熱保護(hù)
狀況排除
※改善周邊環(huán)境,使散熱暢通
※對(duì)過(guò)濾器及冷凝器進(jìn)行清洗
故障狀況 3 冷媒指示燈亮
可能原因
※壓縮機(jī)損壞
※制冷劑泄露
狀況排除
※更換壓縮機(jī),重新抽真空充注制冷劑
※查出泄露處,并重新抽真空加制冷劑
◇若上述措施均不能排除故障,請(qǐng)致電本公司咨詢!
6. 注意警告:
頂置式空調(diào)進(jìn)出風(fēng)口下部嚴(yán)禁放置重要元?dú)饧半娖髁慵乐孤┧畵p壞重要部件!
附錄 1:產(chǎn)品技術(shù)參數(shù)
型號(hào):HSDZA-600W
運(yùn)行電流: <3.8A
功 率: 605W
制冷劑: R134a
制冷量: 600W
防護(hù)等級(jí):內(nèi)循環(huán):IP34 外循環(huán):IP33
允許機(jī)柜內(nèi)溫度設(shè)定范圍:20--38℃(出廠設(shè)定 30℃)
允許使用環(huán)境溫度范圍:-25--45℃
循環(huán)風(fēng)量: 內(nèi)循環(huán) 290m 3/h 外循環(huán):360m 3/h
噪音:60dB
接線方式:進(jìn)線電源為 L,N,PE,單相交流 220V,頻率 50HZ,輸出信號(hào) 1,2 線號(hào)為空調(diào)告警接口,類
型為無(wú)源干接點(diǎn)常開形式,有報(bào)警時(shí)閉合。
蘇州禾久實(shí)電氣設(shè)備有限公司
地 址;江蘇省蘇州市太倉(cāng)市沙溪鎮(zhèn)新北東路
58 號(hào) 1 幢 01 室 1200