蘇州追途電氣設(shè)備有限公司
用
戶
操
作
使
用
說
明
書
ZLJBD-35T-380V50Hz 工業(yè)機柜空調(diào)說明書
目 錄
1. 安全注意事項·······················································································1
2. 安裝要求 ·····························································································1
2-1 安裝位置·························································································2
2-2 安裝方法·························································································3
2-3 電器配線························································································6
2-4 機器排水·························································································6
3. 啟動與運轉(zhuǎn)···························································································6
3-1 運行前后注意事項···········································································6
3-2 機器操作說明··················································································7
4. 維護與保養(yǎng)·························································································7
4-1 定期清潔·······················································································7
4-2 長時間停用時注意··········································································7
5. 故障排除·····························································································8
附錄
一······································································································9
附錄
二······································································································9
1
1. 安 全 注 意 事 項
⑴ 當用戶對本空調(diào)器進行各種操作時,請先詳讀本使用手冊,并注意本手冊
中所提到的注意事項,以避免出現(xiàn)意外情況;
⑵ 請勿用濕手操作,以免引起觸電;
⑶ 當需要保養(yǎng)或維護時,請先切斷所有電源以免引起觸電事故;
⑷ 空調(diào)器上不易放置任何物品,以免滑落造成人員傷害;
⑸ 當機器在運轉(zhuǎn)時,請勿將手指或任何物品伸入進、出風口,以避免人員受
傷或機器損壞;
⑹ 本機器不宜露天放置以免雨水進入機體內(nèi),并且也不適宜于安裝在振動較
大或者移動的設(shè)備上,當客戶必需安裝在此種條件下時,請務(wù)必致電本公司
咨詢;
⑺ 本空調(diào)器為工業(yè)用設(shè)備,當須用于動植物或食品等方面之特殊用途時,請
致電本公司咨詢;
⑻ 禁止自行改裝、修理、拆卸或者移裝,欲進行上述動作前請先向?qū)I(yè)人員
咨詢,以防意外發(fā)生。
2. 安裝要求
本空調(diào)器為頂置式系列(圖一),為使機組能在理想的狀況下工作,在安裝
上請注意以下要求:
圖一 頂置式
電控箱
冷氣機
2
2-1 安裝位置
⑴ 空調(diào)器需安裝在周圍空氣品質(zhì)良好的環(huán)境中,請勿放置于有腐蝕性氣體、
可燃性氣體、粉塵類氣體、油污類氣體等品質(zhì)較差的空氣中;
⑵ 空調(diào)器應安裝在通風良好且熱量易于排放的地方,因為空調(diào)器運行時會
排出熱量,如果空調(diào)器周圍排氣不暢很容易導致其周圍的溫度升高,這將影
響空調(diào)器的制冷效果。見圖二,空調(diào)器進、排風口離墻面的間距應大于
500mm;
⑶ 空調(diào)器周圍請勿放置雜物,以保持空氣暢通流通;
⑷ 本空調(diào)器不宜放置于陽光可以直射的地方,避免因陽光照射而吸熱,影
響冷卻效果。
⑸ 請安裝本空調(diào)器于周圍溫度在 45℃以下的范圍之內(nèi)高溫系列 55℃以下;
⑹ 本機安裝時請注意上下位置擺放正確,絕對不能倒置安裝,前后左右必
須保持垂直,其傾斜角不大于 5°如圖三所示;
⑺ 控制箱內(nèi)正對出風口的電器元件與出風口的最小距離應大于 200mm,因
距離太近電器元件表面易產(chǎn)生水膜現(xiàn)象,從而導致電器故障的發(fā)生。若無法
避免,請在電器元件前增加一塊隔熱材料;并且箱內(nèi)出風口四周的電器元件
與出風口應保持一定的距離,以便減小箱內(nèi)空氣的流通阻力。
⑻ 當空調(diào)器工作時,電控箱四周應該密封,箱門盡量較少打開次數(shù),以便
箱體內(nèi)空氣的溫、濕度能控制在較為理想的狀態(tài)下。
圖二
3
圖 三
錯 誤 正 確 錯 誤 正 確
2-2 安裝方法
⑴ 當機組在搬運、裝卸時,請始終保持設(shè)備處于垂直直立狀態(tài),不要將設(shè)
備長期放在露天場所;
⑵ 為使空調(diào)器的冷卻效果最佳,請將機組直接安裝在電氣柜的外壁上或頂
上(根據(jù)用戶所選機型來決定),請勿采用風管的形式進行送風,如若確實
需要采用風管送風,請先咨詢本公司技術(shù)工程師;
⑶ 空調(diào)器在安裝之前,請先確認好安裝位置的強度是否能承載機組,以免
4
造成人員受傷及設(shè)備損壞,當安裝在電氣柜門上時,最好該扇箱門能固定不
動,當需要打開時請先確認好加在門上的重量不會使整個電氣柜傾倒;
⑷ 電氣柜上必須開孔,以便使冷風能進入電控箱內(nèi),具體的開口尺寸請參
見圖五;
⑸ 箱體開孔時請嚴格參照開口尺寸進行,孔口處的毛刺必須清除,以免劃
傷機組;
⑹ 當長期使用時請注意安裝螺栓是否損壞或脫落,若有而未加處理,將有
可能導致機器掉落而損壞;
⑺ 具體的安裝方式如下:
-5-
安裝方式一:
起吊環(huán)
電控箱
XPE 保溫棉
開口
a. 準備好該類安裝方式的空
調(diào)器
b. 按照開口尺寸在電控箱頂部開好
口,并粘貼好 XPE 保溫綿(若機器
底部自帶,則不需),然后擰下機組
底部四角上的螺帽,并確定好螺栓的
伸出長度(約 15mm)。
電控箱
排水口
C 通過起吊環(huán)用起吊機吊起機組(若
無起吊環(huán)則需人工搬裝),把電源線從
電線孔伸入電控箱內(nèi),然后對好螺栓孔
輕輕放下機器,隨后在電控箱內(nèi)的螺栓
上墊上墊圈并擰緊螺帽。
電控箱內(nèi)側(cè)
d 在機組側(cè)面排水口處連接好排水
管,用抱箍固定好,另一端請引入排水
溝或蓄水桶內(nèi),檢測電源是否與機組匹
配,然后接上電源即可開機使用。
排水管
-6-
2-3 電器配線:
⑴ 機組安裝好后請先檢查電源電壓值是否保持在容許額定值內(nèi),請避免電壓值過高或
過低,若所提供的電壓在額定值±10%以內(nèi),本機組可正常使用;
⑵ 空調(diào)的電器箱在機體內(nèi)部,非專業(yè)維修人員請勿打開電器箱進行操作。機組引出一
根電源線,當安裝好后無需另外接線,將插頭插入電控箱內(nèi)的電源插座即可;
⑶ 在機組的電器回路上請自行安裝斷路器或保護裝置;
⑷ 請準備本機專用電源插座,不要在同一個插座上使用過多電器裝置,否則容易使電
源超出負載,引發(fā)事故。
2-4 機器排水:
本機器自身有除濕功能,當機器運行時,它會慢慢除去電控箱內(nèi)空氣中的部分水分,這
部分水氣就會以液態(tài)的形式排出,排水管就起到排出這部分水的作用,排水管的連接請
注意以下幾點:
⑴ 請先在機器排水口上連接好短接頭,然后把配給的軟管連接上,再用抱箍緊固好連
接處;
⑵ 根據(jù)實際情況排水軟管長度適當即可,過長部分請切除;
⑶ 排水軟管請勿折彎、壓扁、阻塞或出口高于進口,以免排水不暢,從而導致機器內(nèi)
產(chǎn)生淤水嚴重時產(chǎn)生外溢,引起空調(diào)器或者電氣柜故障。
3. 啟動與運行
3-1 運行前后注意事項
⑴ 啟動前請先檢查排水管是否已經(jīng)連接到位,電控箱門是否關(guān)嚴,若均已到位即可插
上電源開始工作;
⑵ 當在運轉(zhuǎn)中需重新啟動空調(diào)器時,請間隔 3 分鐘以上,倘若頻繁啟動且間隔時間過
短會引起機器損傷;
⑶ 當空調(diào)器傾斜時請勿開啟,避免漏水、觸電等情況發(fā)生;
⑷ 空調(diào)器在出廠時溫度點已經(jīng)設(shè)定好為 30℃,若需重新設(shè)定時請控制在允許范圍之內(nèi)
設(shè)定,以免引起機器運行不正常;
⑸ 當機器有異常噪音或異味(焦臭)等現(xiàn)象出現(xiàn)時,請馬上關(guān)閉空調(diào)器,并請專業(yè)人
員進行檢查維修
-7-
使用說明 V1.0.0
簡介:
BTW-289+系列溫控器采用小型化、IP65 等級面板防護設(shè)計,體積小重量輕,操作簡捷安裝方便。適用于小型機柜空
調(diào)系統(tǒng)的溫度控制。
主要功能
1. 制冷,風機自動控制
2. 壓縮機智能保護
3. 多種故障告警,超高溫,低溫告警,系統(tǒng)高壓報警,缺氟報警
4. 外部開關(guān)量輸入檢測,繼電器輸出告警,常開,常閉點自由配置
5. 標準 RS485 通訊接口,Modbus RTU 通訊協(xié)議
規(guī)格尺寸
1.前面板尺寸: 長 78 x 寬 34.5(毫米) 2.安裝開孔尺寸:長 71 x 寬 29(毫米)
3.整機尺寸: 長 78 x 寬 34.5 x 深 71(毫米) 4.傳感器線長:1 米(含探頭長度)
主要技術(shù)指標
感溫元件:NTC 3435/10K 電源電壓:交流型:AC220V±20% 50HZ
設(shè)定范圍:0 ~50℃ 接線端子:連接 2*1.5mm 2顯示范圍:-40~99℃ 或 1*2.5mm 2
的導線
工作環(huán)境:-10~45℃ 負載電流:壓縮機 16A,風機 10A,告警 5A
存儲溫度:-30~70℃ 外 殼:PC + ABS 阻燃
濕 度:5~85%RH (不結(jié)露) 防護等級:IP65(前面板)
操作指南
顯示說明
顯示屏信號說明
圖標 功能 亮 滅 閃爍
壓縮機 啟動 停止 準備制冷,壓縮機正在延時保護
電加熱 運行 ---- 加熱延時開啟
風機 運行 停止 風機延時開啟
set 設(shè)置 參數(shù)設(shè)置狀態(tài) 測控狀態(tài) ----
+ 強啟動 強制啟動壓縮機 退出強啟動 ----面板數(shù)碼管說明
3 位彩色數(shù)碼管顯示測量溫度值和告警代碼;
告警代碼
序 號 顯示代碼 說 明
1 “E01” 溫控傳感器故障(短路或斷路)
3 “E02” 蒸發(fā)器傳感器故障(短路或斷路)
3 “E03” 系統(tǒng)缺氟保護
4 “Hi” 高溫告警
5 “Lo” 低溫告警
8 “LA” 外部無源數(shù)字量輸入告警(系統(tǒng)高壓告警)
10 “FrE 蒸發(fā)器凍結(jié)保護
-8-
按鍵操作
系統(tǒng)參數(shù)設(shè)置
·系統(tǒng)參數(shù)設(shè)置界面進入:
設(shè)置溫度:
測控狀態(tài)下,長按[set]3s,出現(xiàn)[St],再按[set],出現(xiàn)制冷溫度,按〖▲〗或〖▼〗鍵可對參數(shù)進行設(shè)置,設(shè)置
完成后再按[RST]鍵,或者 30s 無按鍵操作,自動保存并回到正常測控狀態(tài)。
設(shè)置內(nèi)部參數(shù):
測控狀態(tài)下,長按[set]3s,出現(xiàn)[St], 按〖▲〗出現(xiàn) Po,再按[set],顯示 0,按〖▲〗或〖▼〗鍵將 Po 設(shè)置
到 55,再按[set],返回 Po,此時按上下鍵,即可選擇其他參數(shù)進行配置。
工作參數(shù)代碼及設(shè)置說明如下表所示:
參數(shù)代碼 設(shè)置功能 設(shè)定范圍 說明 出廠設(shè)定值
St 制冷溫度設(shè)定 15~50℃ 30
Po 密碼 0~99 55 固定不可調(diào) 0
管理員參數(shù)(需要正確的密碼,Po=55)
F00 溫差 1~ 20℃ 5
F01 高溫報警溫度-5~60℃
高溫/低溫
設(shè)定間隔 1℃
50
F02 低溫報警溫度 5
F03 蒸發(fā)風機溫度設(shè)定 0~40℃ 26
F04 蒸發(fā)風機溫差 1~ 9℃ 2
F05 溫控探頭校正 -9~9℃ 0
F06 蒸發(fā)器探頭校正 -9~9℃ 0
F07 高溫報警失效 0~1 0:禁用;1:啟用 1
F08 低溫報警失效 0~1 0:禁用;1:啟用 1
F09 系統(tǒng)缺氟失效 0~1 0:禁用;1:啟用 1
F10 蒸發(fā)器探頭使能設(shè)定 0~1 0:禁用;1:啟用 0
F11 壓縮機工作模式 0~1
0:自動模式(啟用壓縮機)
1:禁用模式
0
F12 風機工作模式 0~1
0:溫控模式
1:常開模式
1
F13 外部輸入告警模式 0~1
0:常閉;
1:常開
0
F14 蜂鳴器報警 0~1 0:禁用;1:啟用 1
F15 壓縮機開機延時時間 1~5 分鐘 3
F16 壓縮機最短持續(xù)運行時間 1~5 分鐘 3
F17 系統(tǒng)開關(guān)機 0:通電關(guān)機,1:通電開機 1
F18 RS485 波特率設(shè)定 0~3
0:4800bps
1:9600bps
2:19200bps
3:115200bps
3
F19 設(shè)備地址 1~64 1
查看蒸發(fā)器溫度
在顯示當前溫度時按一下〖▲〗鍵, 數(shù)碼管顯示制冷設(shè)置溫度值,1S 后恢復顯示當前溫度值。
在顯示當前溫度時按一下〖▼〗鍵, 數(shù)碼管顯示蒸發(fā)器探頭溫度值,1S 后恢復顯示當前溫度值。
控制功能說明:
壓縮機控制
◇當測量溫度 ≥【制冷設(shè)定溫度】 + 【溫差】,且壓縮機停機時間大于【壓縮機開機延時時間】,壓縮機開啟;
◇當測量溫度 ≤【設(shè)定溫度】,且壓縮機開機時間大于【壓縮機最短持續(xù)運行時間】,壓縮機關(guān)閉;
例如:【制冷設(shè)定溫度】為 25 度, 【溫差】為 2 度,則當溫控傳感器檢測溫度高于 27 度時啟動壓縮機,溫度
低于 25 度時關(guān)閉壓縮機,將溫度控制在 25~27 度之間;
◇壓縮機強制啟動:
1.在壓縮機關(guān)閉情況下,按住〖RST〗鍵 5 秒不放,可以強制啟動壓縮機。在壓縮機強制啟動狀態(tài)下,按住〖RST〗
鍵 5
秒不放,可以取消強制啟動壓縮機,壓縮機恢復正常運行。
-9-
2.壓縮機在強制啟動狀態(tài)下持續(xù)運行 30min 后,壓縮機恢復正常運行。
壓縮機延時保護
◇運行過程中壓縮機停機,必須經(jīng)過【壓縮機開機延時時間】才能再次啟動;
◇運行過程中壓縮機開啟,必須經(jīng)過【壓縮機最短持續(xù)運行時間】才能以實際情況停機;
風機控制:
控制器在運行過程中,風機按照如下規(guī)則運行:
? 如果風機設(shè)定為常開,則送風機始終開啟;
? 如果風機設(shè)定為溫控則風機根據(jù)溫控傳感器溫度進行控制。控制條件如下:
◇當測量溫度 ≥【蒸發(fā)風機設(shè)定溫度】 + 【蒸發(fā)風機溫差】,且風機已經(jīng)停機時間大于 1 分鐘,風機開啟;
◇當測量溫度 ≤【蒸發(fā)風機設(shè)定溫度】,且風機開機時間大于 1 分鐘,風機關(guān)閉;
例如:【蒸發(fā)風機設(shè)定溫度】為 23 度, 【蒸發(fā)風機溫差】為 2 度,則當溫控傳感器檢測溫度高于 25 度時啟動風機,
溫度低于 23 度時關(guān)閉風機,將溫度控制在 23~25 度之間;
蜂鳴器功能
每按鍵一次蜂鳴器鳴叫一聲,在參數(shù)設(shè)置確認時長鳴一次,在進行無效操作時蜂鳴器鳴叫三聲;當系統(tǒng)出現(xiàn)故
障
或有外部報警輸入時,如果參數(shù) F13=0,關(guān)閉蜂鳴器報警功能,蜂鳴器不鳴叫報警;如果參數(shù) F13=1,則蜂鳴器
連續(xù)鳴叫報警; 系統(tǒng)恢復正常后,自動消除蜂鳴器報警狀態(tài).高溫、低溫超溫告警
1.當測量溫度 ≥ 【高溫報警溫度】,將產(chǎn)生高溫報警, 當測量溫度 ≤ 【高溫報警溫度】,控制
器取消高溫告警;
2.當測量溫度 ≤ 【低溫報警溫度】,將產(chǎn)生低溫報警, 當測量溫度 ≥ 【低溫報警溫度】+ 2 度,控制
器取消低溫告警;
外部輸入告警 (系統(tǒng)高壓告警)
外部數(shù)字量有以下幾種輸入方式:;
常開:表示在正常情況下外部告警輸入信號為開路狀態(tài),閉合則產(chǎn)生告警。
常閉:表示在正常情況下外部告警輸入信號為閉合狀態(tài),開路則產(chǎn)生告警。
系統(tǒng)高壓告警: 如果 1 小時內(nèi)連續(xù)出現(xiàn) 3 次壓力告警,將一直關(guān)閉壓縮機。手動重新上電可以解除告警。
溫度值校正功能
當測量溫度值與傳感器安裝位置實際溫度有誤差,可通過【溫度修正參數(shù)】進行校正,校正范圍±9.9℃;按一
次〖▲〗
或〖▼〗鍵調(diào)整溫度校正值增或減 0.1℃,按住不放則快速調(diào)整;
系統(tǒng)缺氟(漏氟)保護:
當壓縮機啟動 5 分鐘后,檢測溫控傳感器、蒸發(fā)器傳感器溫度,,如果溫控傳感器溫度高于蒸發(fā)器傳感器溫度 5
度以
上溫差,判定系統(tǒng)正常,否則認定為缺氟保護(漏氟),并顯示報警代碼“E03”。強制關(guān)閉壓縮機。
如果 1 小時內(nèi)連續(xù)出現(xiàn) 3 次缺氟保護,將一直關(guān)閉壓縮機。手動重新上電可以解除告警。
蒸發(fā)器凍結(jié)保護:
當壓縮機啟動 1 分鐘后,檢測蒸發(fā)器傳感器溫度,如果蒸發(fā)器傳感器溫度小于等于-1 度并保持 5 秒,判定蒸發(fā)器
凍結(jié)保護,并顯示報警代碼“FrE”。控制器強制關(guān)閉壓縮機并開啟送風機。當蒸發(fā)器的溫度上升 8 度以上,退出凍
結(jié)保護,控制器恢復正常工作。
告警輸出
告警列表說明
故 障
檢測
條件
推遲
持續(xù)
時間
復位
操作
動作
溫控傳感器故障 隨時 0s 2s 自動
開壓縮機、停電加熱,溫控模式下開蒸發(fā)風機;
取消缺氟保護告警
-10-
蒸發(fā)溫度傳感器故障 隨時 0s 2s 自動 取消缺氟保護告警
壓力保護 隨時 0s 5s 手動 停壓縮機
缺氟保護 壓縮機啟動 5min 5s 手動 停壓縮機
高溫告警 隨時 0s 5s 自動 只告警
低溫告警 隨時 0s 5s 自動 只告警
蒸發(fā)凍結(jié)保護 壓縮機啟動 1min 5s 自動 停壓縮機,開始送風機
告警接口說明
信號名稱 說明
NO 故障輸出(故障時斷開,正常時閉合)
NC 故障輸出(故障時閉合,正常時斷開)
C 公共端
控制器接線示意圖
安 裝步驟
第1步: 將控制器嵌入孔中;
第2步: 通過在設(shè)備的導軌方向
滑動支架來固定控制器,直到將控制器壓實在面板上;
電氣連接
敬告:
◆電氣接線操作必須由有資質(zhì)的技術(shù)人員來完成。
◆使用規(guī)定電源類型以外的電源可能會給系統(tǒng)帶來嚴重損害;
◆盡可能將傳感器、開關(guān)量輸入信號線與感性負載線、電源線分開排線,以避免電磁干擾。絕不能將電源線(包括電力線)
和
485 通訊協(xié)議
本產(chǎn)品支持標準 Modbus RTU 協(xié)議,支持標準 RS485 接口,可與所有支持標準 RS485 接口的設(shè)備通訊。
1. 通訊參數(shù):默認9600,N,8,1,波特率可選;
2. 支持保持寄存器讀寫,支持03,06,16功能碼;
3. 建議應答超時時間設(shè)置大于1000ms;
4 建議輪詢時間間隔設(shè)置大于100ms;
5. R:只讀,W:只寫,R/W:可讀可寫。
6. 下表格是具體寄存器參數(shù)及說明:
地址 功能說明 預設(shè) 範圍 單位 讀寫
0 柜溫探頭溫度(實際溫度×10) - -400~990 ℃ R
1 蒸發(fā)器探頭溫度(實際溫度×10) - -400~990 ℃ R
2 制冷繼電器狀態(tài) - 0:斷開 1:閉合 - R
3 風機繼電器狀態(tài) 0:斷開 1:閉合 R
-11-
4 報警繼電器狀態(tài) - 0:斷開 1:閉合 - R/W
5 制冷溫度設(shè)定值 30 15~50 ℃ R/W
6 控制回差設(shè)定值 5 1~20 ℃ R/W
7 高溫報警溫度 50 1~60 ℃ R/W
8 低溫報警溫度 5 1~60 ℃ R/W
9 蒸發(fā)風機溫度設(shè)定 26 0~40 ℃ R/W
10 蒸發(fā)風機溫差 2 1~5 ℃ R/W
11 蒸發(fā)器探頭使能設(shè)定 0 0:禁用 1:啟用 - R/W
12 壓縮機工作模式 0 0:自動 1:禁用 - R/W
13 風機工作模式 1 0:受控 1:常開 - R/W
14 外部輸入告警模式 0 0:常閉 1:常開 - R/W
15 蜂鳴器報警 1 0:禁用 1:啟用 - R/W
16 壓縮機開機延時時間 3 1~5 Min R/W
17 壓縮機最短持續(xù)運行時間 3 1~5 Min R/W
18 系統(tǒng)上電開關(guān)機 1
0:通電關(guān)機
1:通電開機
- R/W
19 RS485 波特率設(shè)定 1
0:4800
1:9600
2:19200
3:115200
- R/W
20 從機地址(注意:更改之后,上位機讀取
軟件要相應的更改從機地址)
1 1~64 - R/W
21 遠程開關(guān)機(注意:遠程關(guān)機狀態(tài)下,長
按[SET]鍵開機)
1
0:關(guān)機
1:開機
- R/W
4.維護與保養(yǎng)
請定期檢查排水管,并確定無堵塞現(xiàn)象,若排水不良易造成空調(diào)器漏水。請定期清洗空
氣過濾網(wǎng)和冷凝器。對于機器上安裝的是尼龍濾網(wǎng)的可直接從側(cè)面拔出
4-1 定期清潔
⑴ 本公司濾網(wǎng)有兩種樣式,一種為尼龍濾網(wǎng),可直接從側(cè)面拆下,用洗滌水清洗干凈,
并晾干后按原樣裝回,一般每周需清洗一次;另一種為濾芯式濾網(wǎng)(見圖九),當環(huán)境
油污或粉塵大濾芯清洗不干凈時,需要更換新的濾芯,一般半月需要更換一次,;
⑵ 請用中性清洗劑擦拭機體,避免使用硬刷及酸性清洗劑清洗,嚴禁用水沖洗空調(diào)器,
以防發(fā)生觸電事故;
4-2 長時間停用時注意
⑴ 請切斷電源,以防意外;
⑵ 清理冷凝器、過濾網(wǎng)及內(nèi)部油污;
⑶ 請對機器采取防塵措施,延長機器使用壽命。
5. 故障排除
故障狀況 1 電源接通后,室內(nèi)、室外風機不運轉(zhuǎn),溫控器不顯示
可能原因 ※保險絲熔斷
-12-
※停電或無電源
狀況排除
※更換保險絲
※檢查電源狀況
故障狀況 2 過載指示燈亮
可能原因
※環(huán)境溫度過高,導致壓縮機熱保護
※過濾網(wǎng)堵塞或者冷凝器過臟,導致壓縮機熱保護
狀況排除
※改善周邊環(huán)境,使散熱暢通
※對過濾器及冷凝器進行清洗
故障狀況 3 冷媒指示燈亮
可能原因
※壓縮機損壞
※制冷劑泄露
狀況排除
※更換壓縮機,重新抽真空充注制冷劑
※查出泄露處,并重新抽真空加制冷劑
◇若上述措施均不能排除故障,請致電本公司咨詢!
6. 注意警告:
頂置式空調(diào)進出風口下部嚴禁放置重要元氣件及電器零件,防止漏水損壞重要部件!
附錄 1:產(chǎn)品技術(shù)參數(shù)
型號:ZLJBD-35T-380V50Hz
運行電流: 6.55A
功 率: 1650W
制冷劑: R134a
制冷量: 3500W
防護等級:IP54
允許機柜內(nèi)溫度設(shè)定范圍:25--38℃(出廠設(shè)定 30℃)
允許使用環(huán)境溫度范圍:-25-45℃
循環(huán)風量: 內(nèi)循環(huán) 920m 3/h 外循環(huán):1250m 3/h
噪音:65dB
附錄 2:電氣原理圖
-13-
室內(nèi)風機 室外風機 壓縮機
M1 M2 M3
C2 C3
L
N
PE
t℃溫控器
蘇 州 追 途 電 氣 設(shè) 備 有 限 公 司
電話:17311128188