General
Founded in 2006,with 45 million USD turnover per year now,Farady Electric enjoys about 20 years experience in medium voltage section.FARADY Focus on Power transformer /Regulator/Switchgears manufacturing with KEMA/ASTA/ULcertification.
Workshop assembly line photos
General
FARADY developed its own brand pole mounted auto recloser with different functions in orderto full meet different clients'demand.
The vacuum switches are developed base on ACR type original switch.Its pursuit of high reliability,easy to maintain design concepts to create a generation of superior product, is the most reliable electric power system the best option.Different type of expanding switches is optional by client's requirement FARADY all series switches meet the following criteria:
Standard
ANSI/IEEEC37.60/IEC62271-100
ServiceCondition
a)Airtemperature:Maximumtemperature: + 7 0 ^ { \circ } \mathsf { C } :Minimumtemperature: * 4 5 ^ { \circ } \mathsf { C } b)Humidity:Monthlyaverage humidity 9 5 % ;Dailyaveragehumidity 9 0 % c)Altitudeabovesealevel:Maximum installationaltitude: 2 5 0 0 { m } ormore higher. d)Ambient air not apparently polluted by corrosive and flammable gas,vapor etc. e) No frequentviolentshake.
33kV
ACRseriesRecloser
FAR11,FAR15,FAR27,FAR38,Its combined with vacuum interrupter,CT,6EVT,spring mechanismmagneticactuatormechanism,and with relayprotection function.
Farady strives to bring our customers the latest technology and competitive pricing and best service for distribution automatic.The FAR series automatic circuit reclosers can use on overhead distribution lines as well as distribution substation applications for all voltage classes 11kVup to 3 8 \mathsf { k V } at 5 0 / 6 0 \mathsf { H z } power system.and its rated current can reach 800A.
The FAR series automatic circuit reclosers integrates the functions of control, protection,measurement,communication,fault detection,on-line monitoring of closing or opening.
Offering
With optional classes for rated current range: For FAR15,with 800A,Breaking 12.5\~31.5kA.
For FAR27,with 800A,Breaking12.5\~31.5kA.
ForFAR38 with 800A,Breaking12.5\~31.5kA.
With optional relay protection curves for user choice: Instantaneousovercurrent protection.
Timing over-current protection.
Negative sequence over-current protection.
Directional over-current protection(\*).
Over-voltage protection.
Undervoltage protection.
With optional choice by locally or remotely.
With IEC/MODBUS/DNP3.0 communication protocol integrated to SCADA system.
Controller
| Protectionfunctions | ANSI code | Name in Device |
| Phase overcurrent | 50P | Phase.OC1/2/3 |
| Phase Time Overcurrent | 51P | INV-Time-OC |
| Overload | 49 | Overload |
| Ground/Neutra Overcurrent | 50G/50N | Earth fault |
| Sensitive Earth Falut | S.E.F | |
| Ground/Neutral Time Overcurrent | 51G/51N | INV-Time.E.F |
| Auto Reclose | 79 | Reclose |
| Switch On To Fault | SOTF | Manual Acc./Reclose Acc. |
| Cold Load Pickup | CLP | Cold Load |
| Under Voltage | 27 | Under Voltage |
| Over Voltage | 27 | Over Voltage |
| Frequency Relay | 81 | Over/Under Frequency |
| Negative Sequence Instantaneous Overcurrent | 50_2 | NSPTOC |
| Directional Power/Reactive Directional Power | 32P/32Q | Over Power |
Feature
Protection configuration is complete,and all protection functions can be switched on and off flexibly.
12 channels signal input.
4 channelscurrentmeasure.
8 channels voltage measure.
Large capacity flash memory can record at least 10o times of historical events,and no datawill losseventhe powerisoff
Circuits operating loop can be used both the direct or alternating current,selfadaptation open/close brake function,which can co-work with various of breakers,and the operation is simple and reliable.
The device has complete self-inspection function to in-service monitor the working conditions of various parts of the device,ensuring the reliability of the device.
Records
Trip logs SOElogs Alarm logs Operate count
Metering
Phase current IA,IB,IC RMS,residual current I0 Voltage Ua,Ub,Uc,Ur,Us,Ut, Uab,Ubc,Uca,UO(Customer optional) Active power,reactive powerand power factor Frequency
General
Pole-mounted load-break switch (Pole-LBS)applies up to 36 kV 400/630 A, 5 0 / 6 0 ~ { \mathsf { H z } } Pole-LBS associated with a Controller.This SF6 gas-insulated switch can corporate with the Distribution Automation System,and also isolate a faulted section of distribution line from the Control Center.
A simple pole mounting arrangement contribute to quick and low cost installation,and theswitchcan be operated manuallywith aelectronic controller Electronic controller is contained ina stainless steel cabinet for an all weather environmental conditions.Remote monitoring and control can also be Provided mounting wire or wireless Modem in a cabinet.lt shall be principal that this SF6 Gas Load Break Switch shall be used in the following service condition.
33kV
Standard
Every switch is factory filled,hermetically sealed and production tested according to IEC62271-103 prior to shipment.
Service Condition
a)Air temperature:Maximumtemperature: + 7 0 ^ { \circ } \mathsf C ;Minimum temperature: - 2 5 ^ { \circ } \mathsf { C } # b)Humidity:Monthlyaverage humidity 9 5 % ;Dailyaveragehumidity 90 % c)Altitude above sea level:Maximum installation altitude: 2 5 0 0 { m } or more higher. d)Ambient air not apparently polluted by corrosive and flammable gas,vapor etc. e)No frequent violent shake.
Features
·SF6 Gas Insulation
SF6 gas is a nontoxic.non flame able dielectric with excellent arc quenching property.
·Bushing Versatility
Inaddition to the standard porcelain bushing,a variety of options are available including silicon rubber/ porcelain bushing.
·Visible Open/Close
The color coded main contact position indicator(green-open,red closed)is easily visible from the ground.The indicator is connected directly to the main contact drive shaft assemblyassuringaccurate contact status.
·Quick Operation
Spring charged operator is being utilized compression spring to assure quick make and quick-break operation.(<1 Sec.)
·Remote Controllable
Electronic controller isavailable offering local operation RTU-interface for master station control.
·Robust Switch
The switch is manufactured from robust,corrosion resistant,proven materials to ensure long service life and also capable of a number of operations which is an ideal characteristic for pole-mounted equipment.
Descriptions
| Protection functions | Rating | |
| Rated voltage Ur | 12kV/24kV/36kV | |
| Rated current Ir | 630A | |
| Rated Frequency Pr | 50/60Hz | |
| Rated short-time Current Ith | 20kA(r,m,s),4sec | |
| RatedMaking CurrentIma | 50kA(peak),imes | |
| Load Current Breaking | 400/630A,30Times | |
| Cable Charging Current Breaking | 25A,10Times | |
| Line Charging Current Breaking | 15A,10Tims | |
| MagneticCurrent Breaking | 22A,10Times | |
| Mechanism life | Main Contact | 5000Times |
| Ground Contact | 2000Times | |
| Mechanism propeties | Closing Time | |
| Opening Time | ||
| Power frequency withstand voltage | Dry Condition,1minute | 28kV/50kV/70kV |
| Wet Condition,10 seconds | 20kV/40kV/60kV | |
| Impulse withstand voltage(1.2x50μs) | 70kV/125kV/170kV | |
| Controller | Rated voltage | AC220V |
| Power Frequency Withstand Voltage | 2kVrms,1minute | |
| Impulse Withstand Voltage(1.2x50us) | 5kV | |
Note:Moreof thePole mounted gas insulated load break switch information can get from after communication with sale department
Outline Dimension
General
The Farady's new generation FCS capacitor switch is a special electrical field design on vacuum interrupter and switch body insulation for switching capacitive current integrated with single or three phase pole mounted capacitor bank to be reactive power compensation with long mechanical and electrical life design can provides an operational life of over 10,ooomaintenance-free operations.
Using the FCS will result in substantial savings from reduced maintenance and maximized bank uptime and will also improve Power Quality.
TheFCS all complywith relative standard ANSI/IEEE C37.66/IEC60071
Technicaldata
| NO. | Item | Unit | Data | |
| 1 | Rated voltage | kV | 15/27/38 | |
| 2 | Rated current | A | 200 up to 630 | |
| 3 | Rated frequency | Hz | 50/60 | |
| 4 | Power frequency 1min | Dry | kV | 36/60/70 |
| 5 | Wet | 30/50/60 | ||
| 6 | Linghtning impulsewithstand voltage(peakvalue) alternate,opposite/fracture | kV | 95/125/170 | |
| 7 | Rated short circuit breaking current | kA | 12.5/16/20/25 | |
| 8 | Symmetricalfault-makingcurrent | kA | 31.5/40/50/63 | |
| 9 | Rated peakvaluewithstandcurrent | kA | 31.5/40/50/63 | |
| 10 | Symmetrical short time withstand current | kA | 12.5/16/20/25 | |
| 11 | Operationsequence | O-0.5S-CO-180S-C forspring O-0.5S-CO-2S-C for | ||
| 12 | Single capacitor breaking | A | permanentmagnet 630 | |
| 13 | Backtobackcapacitorbankbreaking | A | 400 | |
| 14 | Mechanism life | times | 5000/10000 | |
| 15 | Auxiliary circuit power frequency | kV | 2 | |
| 16 | Auxiliary voltage | V | 240 | |
SalientFeatures-UnisafeCubicle
■The Unisafe cubicle is designed and type tested to meet requirements of IEC62271-
200&60694/1S:3427 ■Metal clad compartmentalised construction-all compartments are segregated from
each other ■with metal sheets ■IP4X degree of protection externally& IP5Xavailable as an option ■Internal arc tested ■Independentexhaust vents forall HTcompartments ■Internal earthing switch (optional) ■Small width panel \boldsymbol { * } 6 0 0 \mathsf {mm } up to 1250Abusbar rating ■The normal service performances are guaranteed under the following conditions -Min.Ambient Temp: - 5 ^ { \circ } C (204號 -Max.Ambient Temp: + 4 0 ^ { \circ } C (20 -Max.Relative Humidity: 9 5 % ■Insulation level of 9 5 \mathsf { k V } available on request ■Option of REF 5 4 2 + ,composite unit for protection,measurement,control,signaling,
Technicaldetails-Unisafecubicle
| Description | Unit | Rating |
| Rated Voltage | kV | 12 |
| Rated Frequency | Hz | 50 |
| RatedBusbarCurrent | A | up to 2000 |
| Short time withstand current (3 sec) | KA kAp | 26.3 66 |
| Insulation levels | kVrms/kVp | 28/75* |
| Widthx Depth× Height up to 1250A above 1250A | mm mm | 600 ×1550×2500 750×1550×2500 |
| Weightwith circuit breaker | Kg | 800 |
| Degree of protection Enclosure Between the compartments | : | IP4X IP2X |
TF
General
VB4P-12
VB4/P medium-voltage indoor vacuum circuit breaker is applicable for three -phase AC power system of rated voltage up to 1 2 - 2 4 \kappa V and frequency50/6oHzwidely used in many fields such as power plant, transformer substation,petrol chemical industy,metallurgy. manuacturing industy.airport,residential area,etc,to control and protect the electric equipment,especially,Itis used for the occasion that nedsinfrequent operation atrated currentor multi-breaking short circuit current,may be mounted in the indoor arinsulatng switchgear like type K28 or AMS,ABB type S1series,etc.This circuit breaker is standards as GB1984-2003 AC high voltage circuit breaker,JB3855 3 . 6 \substack { - 4 0 . 5 \mathsf { k V } } indoor AC High voltage circuitbreaker,DL/T403 Specification of 12-40.5kV indoor High voltage vacuum circuitbreakerfororderaswellaslEC6o694.
This circuit breakeris made with mature APG technology.The application of VB4/P terminal buffer guarantees the indoor terminal is evermorereliable innayoperation environment VB4/P canfullymeet the requirementof GB,DL,IEC,DIN,VDEaswellas standardsofotheradvanced industrialcountries
Service Condition
a)Air temperature:Maximum temperature: + 4 0 ^ { \circ } \mathsf { C } :Minimumtemperature: * 2 5 ^ { \circ } \mathsf { C } b)Humidity:Monthly average humidity 9 5 % ;Dailyaverage humidity 90 % : c)Altitudeabovesealevel:Maximum installationaltitude: 2 5 0 0 { m } d)Ambient air not apparently polluted by corrosive and flammable gas,vapor etc. e)No frequent violent shake
Main technical specifications
| NO. | Item | Unit | Data | ||
| 1 | Rated voltage | kV | 12/17.5 | 24 | 36 |
| 2 | Rated frequency | Hz | 50/60 | ||
| 3 | Rated current | A | 630,4000A | 630,2500 | |
| 4 | 1min Power frequency withstand voltage | kV | 28/38 | 50 | 70 |
| 5 | Lightning impulse withstand voltage | kV | 75/95 | 125 | 170 |
| 6 | Rated short circuitbreaking current (peak) | kA | 50/63/80/100 | ||
| 7 | Rated active load and close circuit breaking current | A | 63 | 50 | 50 |
| 8 | Rated shortbreakingcurrent | kA | 20/40 | ||
| 9 | Rated short circuit making current (peak) | kA | 50/63/80/100 | ||
| 10 | Rated cable(line) chargingbreakingcurrent | A | 50 and 10 | ||
| 11 | Rated capacitor bank switching current | A | 400/600 | ||
| 12 | Ratedwithstand current (peak) | kA | 50/63/80/100 | ||
| 13 | Short time withstand current (4s) | kA | 20,40 | ||
| 14 | Mechanism life | times | 10000 | ||
General
Responded to the international greenhouse gas(GHG) emission reduction and environment friendly target,Farady use uniform electric field technology self-healing dry air insulation technology,no SF6 of GHG and solid epoxy resin waste,Meet the social green low-carbon,environmental protection and energy-saving development trend.
Aironly series environmental protection gas insulated switchgear with compact size, performance stable and reliable,with self-healing ability.Eliminate the risk of insulation loss caused by leakage of SF6 inflatable pressure,and do not adopt the technical scheme of solid insulation with penetration insulation failure caused by local discharge and easy surface pollution flashoverand creepage.It isa new generation of compact environmental protection gas meets the requirements of vacuum technology,environmental gas insulation medium and minimum solid support.
Serviceenvironment
a)Airtemperature:Maximumtemperature: + 4 0 ^ { \circ } C :Minimumtemperature: * 2 0 ^ { \circ } C b)Humidity:Monthlyaverage humidity 9 5 % ;Dailyaveragehumidity 90 % : c)Altitude above sea level:Maximum installation altitude: 2 5 0 0 { m } d)Ambient air not apparently polluted by corrosive and flammable gas,vapor etc. e)No frequentviolent shake
Maintechnicalspecifications
| NO. | Item | Unit | Pamameter |
| 1 | Rated voltage | kV | 12 |
| 2 | Rated current | A | 630 |
| 3 | Rated frequency | Hz | 50/60 |
| 4 | Ratedshort-circuitbreakingcurrent | kA | 25 |
| 5 | Rated short circuit closing current (peak) | kA | 63 |
| 6 | Duration of rated short-time withstand current (s) | s | 4 |
| 7 | Rated short-time withstand current | kA | 25 |
| 8 | Rated peak withstands current | kA | 63 |
| 9 | Rated cable charging switching current | A | 25 |
| 10 | Rated Short Time Power Frequency withstand Voltage | kV | 42 |
| 11 | Rated short-time power frequency withstand voltage (fracture) | kV | 48 |
| 12 | Rated lightning impulsewithstandsvoltage (to earth) | kV | 75 |
| 13 | Rated lightningwithstandsvoltage fracture (to phase) | kV | 85 |
| 14 | Maincircuit resistance | u | 150 |
| 15 | Dry air rated flushing pressure(20℃) | MPa | 0.02 |
| 16 | Dry air minimum working pressure(20℃) | MPa | 0.01 |
General
FGRMU is a ring main unit for the secondary distribution network.FGRMU can be supplied in 10 diferent configurations suitable for most-switching applications in 12/24/36 kV distribution networks.Itis extendable and combined with the SafePlus concept,which is ABB's flexible,modular compact switchgear,they represent a complete solution for 12/24/36 kV secondary distribution networks.FGRMU and SafePlus have identical user interfaces.
FGRMU is a completely sealed system with a stainless steel tank containing allive parts and switching functions.A sealed steel tank with constant atmospheric conditions ensuresa high level of reliabilityaswellaspersonnel safetyanda virtuallymaintenancefree system.
The FGRMU concept offers a choice of either switch-fuse combination or circuitbreaker with relay for protection of the transformer,FGRMU can be supplied with an integrated remote control and monitoring unit.
This product is in conformity with the standards of IEC60420,GB/T11022,GB3804, Gb3906.
Service Condition
a)Air temperature:Maximum temperature: + 4 0 ^ { \circ } C Minimumtemperature 2 0 ^ { \circ } C b)Humidity:Monthlyaverage humidity 9 5 % ;Dailyaveragehumidity 90 % c)Altitudeabovesea level:Maximum installationaltitude: 2 5 0 0 \mathsf { m } : d)Ambient air not apparently polluted by corrosive and flammable gas,vapor etc. e) No frequentviolentshake.
Standardcombinationand itsweight,dimension
Standard combinationand its weight,dimension
| HH HH HH 2 units DV 3 units CCF |
| HH HH HH HH 4units CCCF 5units CCFFF HH |
| HH HH 2 units CF 3 units CFC |
| HH H HF |
Note:we can provide with the RMU according to Special requirement order.
Standardinstruction
·D unit configuration
See standard configuration and features of'Cable connecting module without earth switch module'. ·C unit configuration
See standard configuration and features of'Load break switch module".
·F unit configuration
See standard configuration and features of'Load break switch and fuse combination module'. ·Vunit configuration
See standard configuration and features of'Vaccum switch module".
Standardcombinationsalso includesbelowingconfigurations
Vo Itage indicator ofincoming bushing capacitive character.
S F6 density/pressure monitor(gas meter)with each gas cell.
Ring for lifting.
Operating handle.
Maintechnicalspecifications
| No | Item | Unit | C/F | VModule | ||||
| LoadBreakSwitch 12 | 36 | Circuit Breaker | 36 | |||||
| 1 | Rated voltage | kv | 24 12 24 | |||||
| 2 | Rated current | A | 630(200A/F) | |||||
| 3 | Rated frequency | Hz | 50/60 | |||||
| 4 | 1min Power frequencywithstand voltage | kv | 28 | 50 | 70 | 28 | 50 | 70 |
| 5 | Lightning impulse withstand voltage | kv | 75 | 125/150 170/195 | 75 | 125/150 170/195 | ||
| 6 | Rated transfer current | A | 1700 1400 | 1200 | ||||
| 7 | Rated active load and close circuit breaking current | A | 630 | |||||
| 8 | Rated cable charge breaking current | A | 50&10 | |||||
| 9 | Rated short circuit breaking current | kA | 20 16 | 16/20 | ||||
| 10 | Rated short circuit making current(peak) | kA | 63 | 50 | 40/50 | 63 | 50 | 40/50 |
| 11 | Short time(2s)withstand current, load switch/earth | kA | 25/20 | 20/20 | 16/20 | 25/20 | 20/20 | 16/20 |
| 12 | Rated withstand current(peak) | kA | 63 | 50 | 40/50 | 63 | 50 | 40/50 |
| 13 | Mechanism life | Times | 3000 | 2000 | 10000 | 3000 | 5000 | |
| 14 | Dimension(per unit) | mm | 370×750×1345 | 490910195020 | 4090195020 | |||
Note: For short circuit breaking and peak current is based on Fuse plus combination of F module.
General
This is a new generation of LV Pole Mounted Breaker developed by FARADY Electric in accordancewiththeFrenchmarket
This product uses air as the insulating medium,and adopts a knife contact and grid arc extinguishing structure.
Moreover,this product utilizes an integrated digital trip unit in conjunction with a load indicator to achieve the operating time compliant with the IEC6o947 standard and the cumulative overload tripping function.
Users can adjust the integrated digital trip unit as needed,with three power ratings available:50kVA,100kVA,and160kVA.
The external pointer of the load indicator serves dual purposes:displaying load status and allowing users to rotate it to set the required cumulative trip time.This pointer adjustment feature employs stepless adjustment,offering greater operational convenience.
Users can apply padlocksat the ground-level operating handle to prevent unauthorized personnel from operating the equipment,thereby ensuring power supply security.
Service Condition
Temperature: - 4 0 ^ { \circ } C ~ + 7 0 ^ { \circ } C
Humidity: 100 % (204號
Altitude: <= 2 0 0 0 \mathsf { m }
Wind speed: <= 4 0 \mathsf { m } / \mathsf { s } \bullet \mathsf { H } (204
Note:No fire,no explosion hazards,no chemical corrosion and recurrent severe
vibration
Technicalcharacteristics
| No | Technical Parameters | Unit | Value |
| 1 | ReferenceStandard | / | IEC60947-2 |
| 2 | Rated Voltage | V | 400 |
| 3 | Rated Frequency | Hz | 50 |
| 4 | Rated Current | A | 265 |
| 5 | Number of Poles | / | 4 |
| 6 | Number of Outputs | / | 2 Outputs |
| 7 | Cable Sections | mm² | 50/150 |
| 8 | Breakdown Voltage Pulse/earth At 50Hz Between Poles | / | 20kV 10kV 3kV |
| 9 | Control System | / | Manual |
| 10 | Installation | / | On Post |
Structure
1.Incoming wiring clamp
2.Incoming wiring hole
3.Arc chute grid
4.Operation mechanism
5.Digital trip unit
6.Load indicator
7.Load indicator trip indication
8.Position indicator
9.Operation handle
10.Load trip enable/disable handle
General
MCC LV withdrawable switchgear (hereinafter referred to as device) ismanufactured by standard module through consulting MNS series low voltage switch cabinet of Switzerland ABB Company,and synthetically improved.The device is applicable to the system with AC 5 0 H z ,rated working voltage 660vand below,used as control device for various power generation,transmission,distribution,power transfer and power consumption device.It is widely used in low voltage distribution system of various mining enterprise,tall building and hotel,municipal construction etc.Besides the general land use, after special disposal,it also can be used for marine petrol drilltaken platform and nuclear power station.The device accords with international standard IEC439-1 and national standard GB7251.1.
Service Condition
1.Ambient air temperature: - 5 - + 4 0 and the average temperature should not exceed +35in 24h. 2.Air condition:With clean air,Relative humidity should not exceed 5 0 % at + 4 0 . 1 Higher relative humidity isallowed at lower temperature. E \mathsf { x } . \mathsf { 9 0 % } at ^ { + 2 0 } .Butin view of the temperature change,it is possible that moderate dews willproduce casually. 3.Altitude above sea level shouldnot exceed2o00M. 4.The device is suitable to the transportation and store with following temperature:-25 ^ { + 5 5 } ,in short time (within 24h)it reaches + 7 0 .Under the limiting temperature,device should notsuffer damage that cant recover,and it can works normally under normal conditions. 5.If the above operating conditions not meet users demand.Consult with manufactory. 6.Technical agreement should be signed additionally if the device is used for marine petrol drill taken platform and nuclear power station.
Service Condition
General
GGDACLV fixed type switchgear isapplicable to the distributionsystem with AC 50Hz,rated working voltage 380v,rated current to 3150A below in power station,substation.plant enterprise etc., used forpowertransfer,distributionand controlforpower,lightinganddistributiondevices.The product hascharacteristics of high breaking capacity,fine dynamicand thermal stability,flexibleelectric project, convenient combination,beter serial practicability,novel structure and high protection grade etc.It accords with the standardslEC439 Low voltage complete switch device and control device and GB7251.1 Low voltage complete switch device etc.
Service Condition
1.Ambientair temperature: . 5 ~ + 4 0 and theaverage temperature should not exceed + 3 5 in 24h.
2.Installand use indoors.Altitude above sea level for operation site should not exceed 2000M.
3.Relative humidity should not exceed 5 0 % atmaxtemperature + 4 0 Higherrelativehumidityis allowedat lower temperature. E X . 9 0 % at + 2 0 .But in view of the temperature change,it is possible that moderate dews will produce casually.
4.Installation gradient not exceed 5.
5.lnstall in the places without fierce vibration and shock and the sites insuffcient to erode the electrical components.
6.Any specific requirement,consult with manufactory.
Maintechnical parameters
| Type | Rated voltage(V) | Rated current(A) | bratedngoutrirea | withtedshortotpay) | withstanecuregtla |
| GGD1 | 380 | 1000 600(630)400 | 15 | 15(1S) | 30 |
| GGD2 | 380 | 1500 1600 1000 | 30 | 30(1S) | 63 |
| GGD3 | 380 | 3150(2500)2000 | 50 | 50(1S) | 105 |
Interiorstructure
| Productcode | A | B | C | D |
| GGD06 | 600 | 600 | 450 | 556 |
| GGD06A | 600 | 800 | 450 | 756 |
| GGD08 | 800 | 600 | 650 | 556 |
| GGD08A | 800 | 800 | 650 | 756 |
| GGD10A | 1000 | 600 | 850 | 556 |
| GGD10A | 1000 | 800 | 850 | 756 |
| GGD12 | 1200 | 800 | 1050 | 756 |